REV. 9/23/13678629-H-C Installation, Operation and MaintenanceH SERIESWallmount Heat PumpsR410A SeriesREV. 11/1/09 678629-H-B
10Model No. & Electric Heater Kw [1]VOLT/PHASENO. OF FIELD POWER CKTS.SINGLE-FIELD CIRCUIT DUAL-FIELD CIRCUITMIN. CIRCUIT AMPACITY[2] MAX. OVER CU
11H pg 11.indd 1 9/23/13 9:22 AM
12H pg 12.indd 1 9/23/13 9:19 AM
13H pg 13.indd 1 9/23/13 9:20 AM
14– NOTES –UNIT DIMENSIONS1"KSERVICE DOORFILTER ACCESSDOORDISCONNECTOPENINGJCOMPRESSOR ACCESS DOORFAN ACCESS PANELA - FLANGE WIDTHB - UNIT WIDTHC
1415
678629-V-BThe information in this manual supersedes and replaces the previous instruction/operation manual 678629-V with regards to V Serieswallmount
In all cases, the equipment MUST be installed in accordance withthe installation instructions described in this manual.Set thethermostat to either HEA
TO CLEAN FRESH AIR INTAKE FILTER:A. Follow steps A and B at left “TO CHANGE SYSTEM FILTER”.B. Gently pull out the filter from thebottom.C. Wash the fi
Tap Voltage Range240 Volt 253 - 216208 Volt 220 - 187Seven (7) conductor thermostat wires should be run from thethermostat location to the unit. Therm
A 3/4” drain hose is located on the bottom side of the unit. The drainmay be extended for condensate removal to comply with local codes(use fitting si
EXPLODED PARTS DRAWING — 24 / 30 / 366
7EXPLODED PARTS DRAWING — 42 / 48 / 60
8PART NUMBER DESCRIPTION H424B1 H430B1 H430B3 H436B1 H436B3 H436B4 H448B1 H448B3 H448B4 H460B1 H460B3 H460B42 COMP-BZP24-001 ZP24K5EPFV130 X2 COMP-BZP
9PART NUMBER DESCRIPTION H424B1 H430B1 H430B3 H436B1 H436B3 H436B4 H448B1 H448B3 H448B4 H460B1 H460B3 H460B42 COMP-BZP24-001 ZP24K5EPFV130 X2 COMP-BZP